Wall R-Value Calculator

</> Embed this calculator on your site

This wall r-value calculator adds up every layer in your wall, from siding to drywall, and corrects for the wood studs that let heat bypass the insulation. You get the effective whole-wall R-value, U-factor and the heat lost through your wall area.

Wall assembly section diagram Plan view of a wall showing, from outside to inside, siding, continuous insulation, sheathing, an insulated cavity between studs, and drywall, with the R-value of each layer. OUTSIDE INSIDE Stud Stud (wood) Cavity R-0 SidingR-0 Cont. insul.R-0 SheathingR-0 DrywallR-0 3.5 in cavity depth Effective R-0

About 25% for 16 in o.c., 22% for 24 in o.c. (typical framing).

Estimates only. By using this calculator you agree to our Terms.

</> Embed this calculator on your site

Free for any website, blog, classroom or intranet. No sign-up, no ads inside the embed. Copy the code and paste it into your page.

Preview the embed

How to Use This Wall R-Value Calculator

Pick your stud size, the framing fraction, and the insulation that fills the cavity. Then choose any continuous insulation on the exterior, the sheathing, the siding and the interior finish. Enter your wall area and the indoor and outdoor temperatures if you want a heat loss figure. The result is the effective whole-wall R-value, the U-factor, the R-value through the cavity and through the studs, and a table showing how added exterior foam changes the result. Results update as you change any input.

Why This Matters

The R-value printed on an insulation package is not the R-value of your wall. A 2×6 wall filled with R-21 batts is often sold as an "R-21 wall," but the studs, plates, headers and corners are wood at about R-1.25 per inch, so they conduct heat far faster than the insulation. Roughly 25% of a typical wall's area is framing, and that framing can carry 40–45% of the heat that escapes. A wall with R-20 in the cavity may perform closer to R-16 overall.

Knowing the real number helps you make better decisions. If you are building new, you can compare a 2×4 wall with R-13 batts against a 2×6 wall, or see whether one inch of exterior foam is worth the cost. If you are sizing a furnace or heat pump, the U-factor feeds directly into your heat loss calculation. If you are checking energy code compliance, you can see how your assembly compares with the prescriptive values. Homeowners planning a re-side can find out whether adding R-5 foam under new siding would cut wall heat loss by about a quarter, and builders can show clients why thermal bridging matters.

How It's Calculated

The calculator uses the parallel-path method described in the ASHRAE Handbook of Fundamentals. Heat flows through two paths at once: the insulated cavity and the wood framing. Each path gets its own total R-value, found by adding the R-values of every layer in series:

Rcavity path = Routside film + Rsiding + Rcontinuous insulation + Rsheathing + Rcavity insulation + Rdrywall + Rinside film
Rframing path = the same layers, but with the cavity replaced by wood framing at R-1.25 per inch of depth.

The two paths are then combined by area, using the framing fraction f:

U = f ÷ Rframing path + (1 − f) ÷ Rcavity path
Effective R = 1 ÷ U
Heat loss (BTU/hr) = Area × (Tin − Tout) × U

Air films are fixed at R-0.68 inside and R-0.17 outside (15 mph wind). Cavity insulation is its per-inch value times the cavity depth. The table below lists the per-inch values used.

MaterialR per inch
Fiberglass batt or blown (typical)3.7
Mineral wool batt4.2
Dense-pack cellulose3.6
Open-cell spray foam3.7
Closed-cell spray foam6.5
EPS / XPS / polyiso (aged) / mineral wool board4.0 / 5.0 / 5.0 / 4.2
Softwood framing1.25

Conservative rounding: the effective R-value is rounded down, while the U-factor and heat loss are rounded up, so the tool never overstates insulating performance. Values are typical design numbers; check your product's labeled R-value. The code check compares your nominal cavity and continuous R-values with the prescriptive wood-frame wall table in the 2015/2018 IECC (Table R402.1.2). Your jurisdiction may use a different edition or local amendments, so confirm with your building department. This tool is an estimating aid and is not engineering, permit or inspection approval.

Worked Example

Take a 2×6 wall, 25% framing, fiberglass batts (3.7 × 5.5 = R-20.35), OSB sheathing, vinyl siding and 1/2 in drywall, with 1,000 sq ft of wall at 70°F inside and 20°F outside.

  1. Common layers: 0.17 + 0.61 + 0.50 + 0.45 + 0.68 = R-2.41.
  2. Cavity path: 2.41 + 20.35 = R-22.76.
  3. Framing path: 2.41 + (1.25 × 5.5) = 2.41 + 6.875 = R-9.285 (shown as 9.28 after rounding down).
  4. U = 0.25 ÷ 9.285 + 0.75 ÷ 22.76 = 0.02692 + 0.03295 = 0.05988.
  5. Effective R = 1 ÷ 0.05988 = R-16.7, about 45% of the heat passing through the studs.
  6. Heat loss = 1,000 × 50 × 0.05988 = about 2,994 BTU/hr.

Add 1 inch of XPS (R-5.0) outside the sheathing and the common layers become R-7.41. The framing path rises to R-14.285 and the cavity path to R-27.76, so U falls to 0.04452 and the effective R climbs to about R-22.4. That is a 34% gain from an R-5 layer, because the foam covers the studs too.

Tips & Common Mistakes

Frequently Asked Questions

What is a good R-value for exterior walls?

Under the 2018 IECC, most of the U.S. calls for R-20, or R-13 plus R-5 continuous insulation, in Zones 3–5, and R-20+5 or R-13+10 in Zones 6–8. Warmer Zones 1–2 call for R-13. Those are nominal values, so the effective whole-wall R-value will be lower.

What is the R-value of a 2×4 wall?

A 2×4 wall with R-13 fiberglass batts has a cavity R-value around 13, but the whole-wall effective value is about R-10 to R-11 once the studs, siding, sheathing and drywall are counted. Run the numbers in the calculator above with your own materials.

What is the R-value of a 2×6 wall?

A 2×6 wall with R-20 or R-21 insulation usually comes out near R-16 to R-17 effective with typical sheathing and siding. Adding 1 inch of exterior XPS or similar foam typically lifts that to the low 20s.

How do I convert R-value to U-factor?

U-factor is the inverse of R-value: U = 1 ÷ R. A wall with R-16.7 has a U-factor of about 0.060 BTU/hr·ft²·°F. To convert to metric RSI, divide the R-value by 5.678.

Why is whole-wall R-value lower than the insulation R-value?

Wood studs have a much lower R-value per inch than insulation, so heat flows through them more easily. This is called thermal bridging. The whole-wall value blends the cavity and framing paths by area, which is why it comes out lower than the cavity R-value.

Does the air film count in R-value?

Yes. Still air against the interior surface adds about R-0.68, and the exterior air film adds about R-0.17 under a 15 mph wind. They are small but are included in standard assembly calculations, and this calculator adds them automatically.

Related Tools