Wire Gauge & Ampacity Calculator

This wire gauge ampacity calculator finds the smallest AWG wire for your load, then checks it against breaker size, terminal temperature limits, derating and voltage drop. It follows NEC Table 310.16 / 310.17 and the 240.4(D) small-conductor rule. Codes vary locally, and the result is not permit or inspection approval.

Wire run: source to load SOURCE — V LOAD — A — AWG current flow — ft one-way Run a calculation to fill in your values
NM-B (Romex) cable is always sized from the 60°C column.
Wire rated above the terminals can't use the higher column (NEC 110.14(C)).
Aluminum building wire starts at 12 AWG, so 14 AWG is disabled for it.
Applies to load entries only. A breaker rating is always checked as entered.

Estimates only. By using this calculator you agree to our Terms.

Physics applies at any gauge, but NEC doesn't recognize aluminum building wire below 12 AWG. Move the sliders after calculating to update live.
Estimates only. Values follow NEC Table 310.16 and 310.17 (30°C ambient base, 2020/2023 editions), the 110.14(C) termination rule, 210.19/215.2 continuous-load sizing and 240.4(D). Local amendments vary and other conditions can apply, such as motors, parallel runs, nonmetallic cable rules and special occupancies. Results round toward the safer side (larger wire, standard breaker rounded up) but are not engineering, permit or inspection approval. Have final wiring verified by a licensed electrician and your local inspector.

How to Use This Wire Gauge & Ampacity Calculator

Pick a tab. Find Gauge takes your load in amps, the system voltage and phase, the one-way run length, wire material, insulation rating, breaker/terminal rating, installation method, ambient temperature and number of bundled conductors. It returns the smallest AWG that passes every check, the standard breaker size, the usable ampacity and the voltage drop. Check Wire tests wire you already own. Tell it whether the number you entered is a load or an installed breaker rating, because the 125% continuous factor only applies to loads. Voltage Drop uses sliders so you can see the effect of length and current on any gauge.

Why This Matters

Undersized wire is a quiet fire hazard. When a conductor carries more than its rating, it heats up, insulation hardens and cracks, and connections loosen, often long before a breaker trips. A 40 A continuous EV charger needs a 50 A breaker (40 × 1.25) and 6 AWG copper, not the 8 AWG that looks big enough. A 20 A table saw on 100 feet of 12 AWG at 120 V loses 2 × 12.9 × 20 × 100 ÷ 6,530 = 7.9 V, or 6.6%. The breaker never trips, but the motor runs hot and starts poorly.

Two rules catch people out. NEC 240.4(D) caps 14, 12 and 10 AWG copper at 15, 20 and 30 A breakers, so 14 AWG on a 20 A breaker is never right, even though 14 AWG at 90°C looks rated for 25 A. And NEC 110.14(C) limits you to the rating of the breaker and lug terminals, so premium 90°C wire does not buy extra capacity at the terminals. Electricians, DIYers, solar and RV installers and workshop builders all need ampacity and voltage drop right together.

How It's Calculated

The calculator works in five steps:

  1. Design load: amps × 1.25 for continuous loads, otherwise amps.
  2. Breaker size: round the design load up to the next standard size in NEC 240.6(A): 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100 A and so on.
  3. Usable ampacity is the lowest of three limits: the table ampacity at your insulation rating multiplied by the ambient and bundling factors, the table ampacity at the terminal rating, and the 240.4(D) cap.
  4. Pick the smallest AWG whose usable ampacity is at least the breaker size. This is deliberately conservative, because NEC 240.4(B) would sometimes allow the next breaker size above the wire's rating.
  5. Voltage drop check: if drop exceeds 3%, step up to the first gauge that meets 3%. If none does, the tool reports its largest size and says the drop is still too high.
Single-phase: VD = (2 × K × I × L) ÷ CM
Three-phase: VD = (1.732 × K × I × L) ÷ CM
VD% = VD ÷ system voltage × 100

K is 12.9 for copper and 21.2 for aluminum (ohm·cmil/ft). I is the load current, L is the one-way length in feet, and CM is the conductor's circular-mil area. Voltage drop uses the actual load, not the 125% figure. The "auto" terminal setting follows NEC 110.14(C): the 60°C column for circuits of 100 A or less, 75°C above that. The code allows 75°C for some larger conductors on smaller circuits, but the tool stays on the safer 60°C side. Choose 75°C only if your breaker and equipment are marked for it.

Worked Example

A permanently wired 20 A continuous heater, 120 V single-phase, 60 ft from the panel. Copper 75°C (THWN) wire in conduit, auto terminals, 30°C ambient, three or fewer conductors. These are the tool's default Find Gauge inputs.

  1. Design load: 20 × 1.25 = 25 A. The standard breaker is 25 A.
  2. Terminals: the breaker is 100 A or less, so the 60°C column limits the terminals.
  3. 14 AWG: 20 A (75°C) vs. terminal 15 A vs. cap 15 A gives 15 A usable, which is too small.
  4. 12 AWG: 25 A vs. terminal 20 A vs. cap 20 A gives 20 A usable, which is still too small.
  5. 10 AWG: 35 A vs. terminal 30 A vs. cap 30 A gives 30 A usable, which is at least 25 A, so it passes.
  6. Voltage drop: 2 × 12.9 × 20 × 60 ÷ 10,380 = 2.98 V, or 2.49% of 120 V. That is under 3%.

Result: 10 AWG copper with a 25 A breaker.

Tips & Common Mistakes

Frequently Asked Questions

What AWG wire for a 20-amp circuit?

For a non-continuous 20 A load, 12 AWG copper is standard, because 240.4(D) caps 12 AWG at a 20 A breaker. If the load is continuous, it must be sized at 125%, which means a 25 A breaker and normally 10 AWG copper.

What's the difference between AWG and wire diameter?

AWG is an inverse scale, so a lower number means thicker wire. Cross-sectional area roughly doubles every 3 gauge steps, and diameter doubles about every 6. Ampacity grows more slowly than area: going from 10 AWG (30 A at 60°C) to 4 AWG (70 A) takes six steps and quadruples the area but only a bit more than doubles the ampacity.

How much voltage drop is acceptable?

The NEC informational notes recommend no more than 3% on a branch circuit or feeder and 5% overall. These are recommendations, not enforceable limits. Sensitive electronics and long motor runs do better under 2%.

Can I use aluminum wire instead of copper?

Yes, select Aluminum. The calculator uses aluminum's higher resistivity (K = 21.2) and its own ampacity column in Table 310.16, which usually means going up about two sizes. Free-air aluminum values aren't included, so conduit values are used instead. Aluminum building wire below 12 AWG isn't recognized.

What is the NEC 240.4(D) small-conductor rule?

It limits overcurrent protection for 14, 12 and 10 AWG copper to 15, 20 and 30 A. For aluminum, 12 AWG is capped at 15 A and 10 AWG at 25 A. The tool applies these caps automatically, so it never pairs a small wire with an oversized breaker.

Why doesn't 90°C wire let me use a smaller gauge?

The lowest of the wire, terminal and 240.4(D) limits always governs, and most breakers and lugs are only rated for 60°C or 75°C. 90°C wire mainly helps by giving more headroom before ambient heat or bundling derating drops you below the terminal limit.